← Back to Field App

Electric / Diesel Fire Pump Churn / Inspection (circle one)

KEY: G = Good · NG = No Good · NA = Not Applicable · Ddiesel only · Eelectric only
Job Number
Site Address
Date
1. Equipment · Upload photos of equipment
2. Pre-start fluids & batteriesDIESEL only — skip for electric
DBlock / water-jacket heater ON (if eq.)G ☐ NG ☐ NA ☐
DBanks 1 & 2 OK (term./electrolyte/pilots)G ☐ NG ☐ NA ☐
Fuel level
Engine hours hrs
Batt V b1
Batt V b2
Charge A b1
Charge A b2
3. Room / leaks / packing
Pump room heat / lights / housekeeping; louvers freeG ☐ NG ☐ NA ☐
System offline / isolate FP discharge as requiredG ☐ NG ☐ NA ☐
Exposed piping leaks / packing (pre-run)G ☐ NG ☐ NA ☐
DSite flags (strainer / tank / fuel shutoffs / sensing)G ☐ NG ☐ NA ☐
DStrainer cleaned (raw-water / HX)G ☐ NG ☐ NA ☐
4. Auto start (sensing line / auto)
Start method OK (auto primary)G ☐ NG ☐ NA ☐
Sensing line for fire pumpG ☐ NG ☐ NA ☐
Sensing line for jockey pumpG ☐ NG ☐ NA ☐
DStarter 1 crankG ☐ NG ☐ NA ☐
DStarter 2 crankG ☐ NG ☐ NA ☐
Start method (circle): Sensing-line / Auto timer / Manual / Other
FP start PSI
Jockey start PSI
Jockey stop PSI
5. Diesel / electric start & run verificationClean start & run.
Engine / motor starts cleanly (no abnorm. noise/vib)G ☐ NG ☐ NA ☐
Accelerates to rated speed / controller OKG ☐ NG ☐ NA ☐
No abnormal alarms (D: oil/temp/overspeed · E: phase/power-fail/OC)G ☐ NG ☐ NA ☐
Controller indicates RUN / normalG ☐ NG ☐ NA ☐
6. Churn / run — key readingstypically 30 min diesel · 10 min electric
DOil PSI
RPM
DCool °F
DLoop P psi
DBatt V
EAmps
EVolts
Suction psi
Disch. psi
7. During-run OK checks
DHX / raw-water cooling flow OKG ☐ NG ☐ NA ☐
Circ. relief OK (if eq.); no overheatG ☐ NG ☐ NA ☐
Packing drip OK; no packing/bearing/casing OHG ☐ NG ☐ NA ☐
Unusual noise/vib (none = Good)G ☐ NG ☐ NA ☐
Engine / motor / bearings temp OK (no overheat)G ☐ NG ☐ NA ☐
Disch. water temp OK / no OH shutdownG ☐ NG ☐ NA ☐
8. Restore to service / controllers AUTO
Valves open/normal; system back in serviceG ☐ NG ☐ NA ☐
Controllers AUTO; alarms/mon. restoredG ☐ NG ☐ NA ☐
Notes
Name / Signature